Frost protection thermostat (2-phase) with continuous and switching output
Application
Electronic frost protection thermostat with fully active capillary for monitoring air conditioning systems, heat exchangers, heating registers and other systems against freezing. The limit value undercut is measured at the coldest measuring point on the sensor rod. A safety shutdown occurs in the event of a capillary break, voltage failure or damage.
Technical Data
Measuring range: | 0...+15°C |
---|---|
Ambient temperature: | -15...+50°C |
Power supply: | 24V AC/DC |
Output: | 1 x 0... 10V (= 0... + 15°C) |
Power consumption: | max. 10mA at 24V DC |
Accuracy: | ±1K (at 10°C) |
Switching stage hysteresis: | 2K |
Sensor dimensions: | Ø=2mm, nominal lengths 3m and 6m |
Rod: | Copper, fully active probe length |
Housing: | Plastic, color light gray |
Electr. connection: | by means of screw terminals 0.14... 1.5mm² |
Switch-on run-in time: | <1min |
Response time: | t 90<5s |
Permissible humidity: | <95% r.H. uncondensed air |
Protection type: | IP65 (EN 60529) |
Protection class: | III (EN 60730) |