Frost protection thermostat (mechanical) with switching output
Application
Frost protection thermostats with automatic or manual reset for air or water temperature monitoring to protect heat exchangers, water circulation systems and heating registers against freezing. The devices have a sealable setpoint adjustment. A safety shutdown occurs in the event of a capillary break, voltage failure or damage.
Technical Data
Switching capacity: | 15 (8) A; 24-250V AC |
---|---|
Switching differential: | 2K |
Capillary material: | Copper |
Contact: | Dust-encapsulated microswitch as a single-pole potential-free changeover contact |
Setting range: | -10... +12°C |
Ambient temperature: | -10... +55°C |
Reset: | TF-X automatically |
Installation: | The housing must be mounted in such a way that the ambient temperature on the housing cannot be lower than the setpoint set on the controller. |
Probe response length: | ca. 40cm |
Housing: | ABS / polycarbonate, gray / transparent |
Protection type: | IP65 (EN 60529), IP54 optional |
Protection class: | I (EN 60730-1) |