Contact temperature transmitter with switchable measuring ranges
Description
Contact temperature transmitters in a robust plastic housing with clamping band are used for temperature detection on pipes (f. e. cold and hot water) or heating pipes and convert the measured value into a linear output signal 0-10 V or 4-20 mA. With the supplied pipe clamp, the contact block is attached directly to the pipe. The measuring ranges are switched by DIP switches.
Technical Data
Measuring ranges: | -50...+50°C, -20...+80°C, 0...+50°C, 0...+100°C, 0...+160°C, -50...+160°C selectable with dip switch (other measuring ranges optional) |
---|---|
Voltage supply: | 24 VAC ± 10% (for voltage output) |
Ambient temperature: | -30...+70°C |
Sensor: | Pt100 Class B, DIN EN 60751 |
Connection type: | 2-/ 3-wire connection |
Process connection: | Pipe clamp |
Strap dimensions: | Ø=13-92 (1/4 - 3“), 300mm |
Housing: | Box shaped, synthetic, white colour |
Insulating resistance: | >/= 100MOhm, by 20°C (500V DC) |
Protection type: | IP65 according EN 60529 |
Protection class: | III according EN 60730 |
Accessories: | Heat transfer paste |